Chilled water system configuration can be roughly devided into the following three types:
Load is controlled by 3-way valves installed in the downstream of cooling coil by bypassing waterflow as needed. Water
Capacity is controlled by VFD installed on secondary pumps. Primary loop water flow should be equal to or more than secondary loop water flow. Otherwise, the heated secondary loop water in the downstream of cooling coil would bypass the chiller and enter directly to the cooling again, disrupting the system. The bypass water from primary to secondary loop flows through a piping called decoupler. The flow in decouple should be one directional.
Capacity is controlled by VFDs installed on primary pumps. A bypass valve is needed to maintain the minimum required flow. If the water speed through the evaporate tube is too low, water can freeze and rupture the tube.
CPF | CPF VSF | VPF | |
---|---|---|---|
Load control device | 3-way valves on CC downstream | VFD on secondary loop | VFD on primary loop |
Modulated variable | Delta T | Flow rate | Flow rate |
Bypass piping | No | Yes | Yes |
Bypass valve | No | No | Yes |
Hubbard, R.S.. (2011). Energy impacts of chilled-water-piping configuration. 83. 20-27.